Hotline 24/7: 0986951455
Việt Nam English
Sản phầm nổi bật

Contactors - J7MN

Mã sản phẩm: J7MN
Tình trạng: Có hàng

Liên hệ
Liên hệ

MPCB system (motor protection CLASS 10)

 

 

• Rotary and switch types

• Rated operational current = 12 A, 25 A, 50 A and 100 A

• Switching capacity up to 12.5 A = 100 kA/400 V

• Fixed short-circuit release = 13 x Iu

• Overload release adjustable 0.7 - 1 x Iu

• Single phasing sensivity

 

Auxiliary contact modules

 

 

• ON/OFF indication for MPCB front mounting and side mounting

• Trip indication for MPCB side mounting

 

Accessories

 

 

• Undervoltage release

• Shunt release

• Three phase busbar system up to 5 MPCB

• Moulded plastic enclosures (IP55)

• Moulded plastic front plates (IP55)

• Door coupling rotary mechanisms (black and red/yellow)


Components for Fuseless Load Feeders, DIN-Rail Mounting

Type of coordination „1“ 3 x 415 V 10 kA (other conditions on request)

 

Motor 3~400V 
kW
Setting range 
A
Circuit-breaker 
Type
Contactor 
220-230V 50Hz 
Type
Link module 
Type
DIN-rail adapter 
Type
- 0.11 - 0.16 J7MN-25-E16 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.14 - 0.2 J7MN-25-E2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.06 0.18 - 0.25 J7MN-25-E25 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.09 0.22 - 0.32 J7MN-25-E32 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.28 - 0.4 J7MN-25-E4 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.12 0.35 - 0.5 J7MN-25-E5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.18 0.45 - 0.63 J7MN-25-E63 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.55 - 0.8 J7MN-25-E8 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.25 0.7 - 1 J7MN-25-1 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.37 0.9 - 1.25 J7MN-25-1E25 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.55 1.1 - 1.6 J7MN-25-1E6 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.75 1.4 - 2 J7MN-25-2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 1.8 - 2.5 J7MN-25-2E5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
1.1 2.2 - 3.2 J7MN-25-3E2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
1.5 2.8 - 4 J7MN-25-4 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 3.5 - 5 J7MN-25-5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
2.2 4.5 - 6.3 J7MN-25-6E3 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
3 5.5 - 8 J7MN-25-8 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
4 7 - 10 J7MN-25-10 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
5.5 9 - 12.5 J7MN-25-12E5 J7KN-14-10 230 J74MN-VD-12 J74MN-HU
7.5 11 - 16 J7MN-25-16 J7KN-18-10 230 J74MN-VD-12 J74MN-HU
- 14 - 20 J7MN-25-20 J7KN-22-10 230 J74MN-VD-25 J74MN-HU
- 17 - 22 J7MN-25-22 J7KN-22-10 230 J74MN-VD-25 J74MN-HU
11 20 - 25 J7MN-25-25 J7KN-22-10 230 J74MN-VD-25 J74MN-HU

 

Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660

 

This table shows the rated ultimate short-circuit breaking capacity Icu and the rated service short-circuit breaking capacity Icsof the J7MN circuit-breakers with different operational voltages as a function of the rated current In of the circuit-breakers.

The circuit-breakers can be fed at the top or bottom supply terminals without any reduction of the rated data.

If the short-circuit current exceeds the rated short-circuit breaking capacity of the circuit-breaker specified in the tables at the installation point, a back-up fuse is to be used.

The maximum rated current for the back-up fuse is specified in the tables. These fuses are only suitable for the short-circuit-currents as indicated on the fuses.

 

 

Circuit- 
breaker 
Type
Rated 
current 
In 
A
up to AC 240V *1 up to AC 400V *1 
up to AC 415V *2
up to AC 440V *1 
up to AC 460V *2
Icu 
kA
Ics 
kA
max. 
fuse 
(gL/gG) 
A
Icu 
kA
Ics 
kA
max. 
fuse 
(gL/gG) 
A
Icu 
kA
Ics 
kA
max. 
fuse 
(gL/gG) 
A
J7MN-12 0.16 to 0.8 100 100 -- 100 100 -- 100 100 --
1 100 100 -- 100 100 -- 100 100 --
1.25 100 100 -- 100 100 -- 100 100 --
1.6 100 100 -- 100 100 -- 100 100 --
2 100 100 -- 100 100 -- 100 100 --
2.5 100 100 -- 100 100 -- 100 100 --
3.2 100 100 -- 100 100 -- 10 10 40
4 100 100 -- 100 100 -- 10 10 40
5 100 100 -- 100 100 -- 10 10 50
6.3 100 100 -- 100 100 -- 10 10 50
8 100 100 -- 50 12.5 80 *3 10 10 63
10 100 100 -- 50 12.5 80 *3 10 10 63
12 100 100 -- 50 12.5 80 *3 10 10 80
J7MN-25 0.16 to 1.25 100 100 -- 100 100 -- 100 100 --
1.6 100 100 -- 100 100 -- 100 100 --
2 100 100 -- 100 100 -- 100 100 --
2.5 100 100 -- 100 100 -- 100 100 --
3.2 100 100 -- 100 100 -- 100 100 --
4 100 100 -- 100 100 -- 100 100 --
5 100 100 -- 100 100 -- 100 100 --
6.3 100 100 -- 100 100 -- 100 100 --
8 100 100 -- 100 100 -- 50 25 63 *3
10 100 100 -- 100 100 -- 50 25 80 *3
12.5 100 100 -- 100 100 -- 50 25 80 *3
16 100 100 -- 50 25 100 *3 20 10 80
20 100 100 -- 50 25 125 *3 20 10 80
22 100 100 -- 50 25 125 *3 20 10 100
25 100 100 -- 50 25 125 *3 20 10 100
J7MN-50 25 100 100 -- 50 25 125 *3 30 15 100
32 100 100 -- 50 25 125 *3 30 15 125
40 100 100 -- 50 25 160 *3 30 15 125
45 100 100 -- 50 25 160 *3 30 15 125
50 100 100 -- 50 25 160 *3 30 15 125
J7MN-100 63 100 100 -- 50 25 160 *3 40 20 160
75 100 100 -- 50 25 160 *3 40 20 160
90 100 100 -- 50 25 160 *3 40 20 160
100 100 100 -- 50 25 160 *3 40 20 160

 

 

Circuit- 
breaker 
Type
Rated 
current 
In 
A
up to AC 500V *1 
up to AC 525V *2
up to AC 690V *1
Icu 
kA
Ics 
kA
max. 
fuse 
(gL/gG) 
A
Icu 
kA
Ics 
kA
max. 
fuse 
(gL/gG) 
A
J7MN-12 0.16 to 0.8 100 100 -- 100 100 --
1 100 100 -- 100 100 --
1.25 100 100 -- 2 2 20
1.6 100 100 -- 2 2 20
2 10 10 35 2 2 35
2.5 10 10 35 2 2 35
3.2 3 3 40 2 2 40
4 3 3 40 2 2 40
5 3 3 50 2 2 50
6.3 3 3 50 2 2 50
8 3 3 63 2 2 63
10 3 3 63 2 2 63
12 3 3 80 2 2 80
J7MN-25 0.16 to 1.25 100 100 -- 100 100 --
1.6 100 100 -- 100 100 --
2 100 100 -- 8 8 25
2.5 100 100 -- 8 8 25
3.2 100 100 -- 8 8 32
4 100 100 -- 6 3 32
5 100 100 -- 6 3 32
6.3 100 100 -- 6 3 50
8 42 21 63 6 3 50
10 42 21 63 6 3 50
12.5 42 21 80 6 3 63
16 10 5 80 4 2 63
20 10 5 80 4 2 63
22 10 5 80 4 2 63
25 10 5 80 4 2 63
J7MN-50 25 12 6 80 5 3 63
32 10 5 100 4 2 63
40 10 5 100 4 2 63
45 10 5 100 4 2 63
50 10 5 100 4 2 80
J7MN-100 63 12 6 125 6 3 80
75 8 4 125 5 3 100
90 8 4 125 5 3 125
100 8 4 125 5 3 125

 

*1. 10% overvoltage 
*2. 5% overvoltage 
*3. Back-up fuse required if short-circuit current at installation point > 50 kA 
-- No back-up fuse required.

Main Circuit

 

Type J7MN-12 J7MN-25 J7MN-50 J7MN-100
Number of poles 3 3 3 3
Max. rated current Inmax (=max. rated operational 
current Ie)
A 12 25 50 100
Permissible ambient 
temperature
Storage/transport °C -50 to +80
Operation °C -20 to +70 *1
Permissible rated 
current at 
temperature inside 
cubicle of:
+60 °C % 100
+70 °C % 87
Circuit-breaker 
inside enclosure 
Permissible rated 
current at 
temperature inside 
enclosure of:
+60 °C % 100
+70 °C % 87
Rated operational voltage Ue V 690 *2
Rated frequency Hz 50/60
Rated insulation voltage Ui V 690
Rated impulse withstand voltage Uimp kV 6
Utilization category IEC 60 947-2 (circuit-breaker) A
IEC 60 947-4-1 (motor starter) AC-3
Class acc. to IEC 60 947-4-1 10
DC short-circuit 
breaking capacity 
(time constant 
t = 5 ms)
1 conducting path DC 150 V kA 10
2 conducting paths in series 
DC 300 V
kA 10
3 conducting paths in series 
DC 450 V
kA 10
Power loss Pv per 
circuit-breaker 
dependent on rated 
current In 
(upper setting range) 

R per conducting path 
= P/(I2 × 3)
In -> to 1.25 A 
In -> 1.6 to 6.3 A 
In -> 8 to 12 A


W


7


-


-


-
In -> 1 to 6.3 A 
In -> 8 to 16 A 
In -> 20 to 25 A


W


-


8


-


-
In -> to 25 A 
In -> 32 A 
In -> 40 to 50 A


W


-


-
12 
15 
20


-
In -> to 63 A 
In -> 75 to 90 A 
In -> to 100 A


W


-


-


-
20 
30 
38
Shock resistance acc. to IEC 68 Part 2-27 g 25 25 25 25
Degree of protection acc. to IEC 60 529 IP 20 IP 20 IP 20 *3 IP 20 *3
Shock hazard 
protection
acc. to DIN VDE 0106 Part 100 safe against finger touch
Temperature 
compensation
acc. to IEC 60 947-4-1 °C -20 to +60
Phase failure 
sensitivity
acc. to IEC 60 947-4-1 yes
Explosion protection acc. to EC Directive 94191 EC yes *4
Isolator 
characteristics
acc. to IEC 60 947-3 yes
Main and EM. STOP 
switch characteristics
acc. to IEC 60 204-1 (VDE 0113) yes *5
Safe isolation between 
main and auxiliary 
circuits
acc. to DIN VDE 
0106 Part 101
up to 
400 V +10 %
yes
up to 
415 V +5 %
yes
Mechanical endurance operating cycles 100 000 100 000 50 000 50 000
Electrical endurance 100 000 100 000 25 000 25 000
Max. operating frequency per hour (motor starts) 1/h 15 15 15 15
Permissible mounting position any. acc. to IEC 60 447 start command "I" right- 
hand side or top

 

*1. Over +60°C current reduction 
*2. 500 V with moulded-plastic enclosure 
*3. Terminal compartment IP00 
*4. KEMA-test certification on request 
*5. With appropriate accessories

Conductor cross-sections for main Circuit

 

Type J7MN-12 J7MN-25 J7MN-50 J7MN-100
Terminal type Screw-type Screw-type Box terminal Box terminal
Terminal screw Pozidriv size 2 Pozidriv size 2 Pozidriv size 2 Allen screw 4 mm
Tightening torque Nm 0.8 to 1.2 2 to 2.5 3 to 4.5 4 to 6
Conductor 
cross- 
sections
solid mm2 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 16)
mm2 2 x (0.75 to 2.5) 2 x (2.5 to 6) - -
mm2 1 x (0.5 to 4)      
finely stranded with 
end ferrule
mm2 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 35)
mm2 2 x (0.75 to 2.5) 2 x (2.5 to 6) 1 x (0.75 to 25) 1 x (2.5 to 50)
mm2   1 x (1 to 10)    
stranded mm2 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 25) 2 x (10 to 50)
mm2 2 x (0.75 to 2.5) 2 x (2.5 to 6) 1 x (0.75 to 35) 1 x (10 to 70)
mm2 1 x (0.5 to 4) 1 x (1 to 10)    
AWG-wires, solid or 
stranded
AWG 2 x (18 to 14) 2 x (14 to 10) 2 x (18 to 3) 2 x (10 to 1/0)
AWG - - 1 x (18 to 2) 1 x (10 to 2/0)
conductor bar (number 
x width x thick)
mm - - 2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8)
  mm - - - 18 x 10
mm2 - - - up to 2 x 70

 

Auxiliary switches

 

Switching capacity Control voltage
Front transverse 
auxiliary switch 
with 1 NO + 1 NC
Rated operational 
voltage Ue
AC V 24 230    
Rated operational 
current Ie/AC-15
A 2 0.5    
Rated operational 
current Ie/AC-12 Ith
A 2.5 2.5    
Rated operational 
voltage Ue
DC L/R 
200 ms
V 24 48 60  
Rated operational 
current Ie/DC-13
A 1 0.3 0.15  
Lateral auxiliary 
switch and 
signalling switch
Rated operational 
voltage Ue
AC V 24 230 400 690
Rated operational 
current Ie/AC-15
A 6 6 3 1
Rated operational 
current Ie/AC-12 Ith
A 10 10 10 10
Rated operational 
voltage Ue
DC L/R 
200 ms
V 24 110 220 440
Rated operational 
current Ie/DC-13
A 2 0.5 0.25 0.1
Undervoltage 
release
Power consumption during pick-up VA/W 20.2/13
uninter-rupted 
duty
VA/W 7.2/2.4
Response voltage trip V 0.7 to 0.35 × Us
pick-up V 0.85 to 1.1 × Us
Max. opening time ms 20
Shunt release Power consumption during pick-up AC VA/W 20.2/13
DC W 13 to 80
Response voltage acc. to IEC 60 947-1, 
trip
V 0.7 to 1.1 × Us
Max. opening time ms 20
Short-circuit 
protection for 
auxiliary and 
control circuits
Fuse gL/gG A 10
Miniature circuit breaker C- 
characteristic
A 6 *1
Conductor 
cross-sections 
for auxiliary and 
control circuits
  Screw-type Pozidriv size 2
solid mm2 2 x (0.5 to 1.5)/2 x (0.75 to 2.5)
finely stranded with ferrule mm2 2 x (0.5 to 1.5)/2 x (0.75 to 2.5)
stranded mm2 2 x (0.5 to 1.5)/2 x (0.75 to 2.5)
AWG-wires, solid or stranded AWG 2 x (18 to 14)

 

*1. Prospective short-circuit current < 0.4 kA.


Bình luận facebook
Bình luận Form
go top