Power supply voltage |
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC |
Operating voltage range |
85% to 110% of rated supply voltage |
Power consumption |
100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA)
24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) |
Sensor input |
Any of the following can be selected (i.e., fully universal input).
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V |
Input impedance |
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N.) |
Control method |
ON/OFF control or 2-PID control (with auto-tuning) |
Control
output |
Relay output |
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output
(for driving SSR) |
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit |
Current output |
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 * |
Linear voltage output |
0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000 |
Auxiliary
output |
Number of outputs |
2 max. |
Output specifications |
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Event
input |
Number of outputs |
2 |
External contact
input specifications |
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. |
Current flow: Approx. 7 mA per contact |
Logic
operations |
Number of operations |
8 max. (Combinations can be made using work bits.) |
Operations |
• Logic operation:
Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.)
• Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
• Output inversion: Possible |
Outputs |
One work bit per operation |
Work bit
assignments |
Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. |
Transfer
outputs |
Number of outputs |
1 max. |
Output
specifications |
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 |
RSP input |
Not supported |
Setting method |
Digital setting using front panel keys |
Indication method |
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: PV: 11 mm, SV: 6.5 mm |
Bank switching |
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) |
Other functions |
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment |
Ambient operating temperature |
-10 to 55°C (with no condensation or icing), for 3-year warranty: -10 to 50°C |
Ambient operating humidity |
25% to 85% |
Storage temperature |
-25 to 65°C (with no condensation or icing) |